HIGH PRESSURE REFRIGERATED AIR DRYER - PET SERIES
SALIENT FEATURES
- Complete range with ozone friendly refrigerant
- Compact in size
- Wide range
- Lower power consumption
- Reliable components
- Consistent dew point
GENERAL FEATURE
- Copper "Tube in Tube" non corrosive heat exchanger, designed to have lower pressure drop and higher efficiency contains in built centrifugal moisture separator having dead zone to avoid carry over of condensate.
- PUF insulation for heat exchanger assembly.
- Electronic timer operated Auto Drain Valve.
- Universally available refrigeration components like Compressor , Fan motor, Filter dryer, Expansion Valve etc.
- Non cyclic refrigeration systems , with the help of hot gas bye pass Solenoid Valve , for varying load condition and seasonal adjustments.
- GEM PET Series Dryers are filled with "Ozone Friendly" R134a refrigerant.
INSTALLATION
GEM PET dryers are pre wired/pre piped and are ready to install and operate.
ELECTRICALS
Electrical is in accordance with application code and uses international components.
SERVICEABILITY
A "Fit and Forget" unit and requires least maintenance (Trouble shooting and installation guidelines are given in manual that will be supplied along with dryer).
TECHNICAL SPECIFICATIONS
Base Model | Air Flow | Ref. Power | Electrical Connection* | Inlet / Outlet | Dimensions | Weight | ||||
(mm) | ||||||||||
CFM | m³/h | kW* | 220V / | 415V / | BSP | A | B | C | kg. | |
1Ø/50Hz | 3Ø/50Hz | |||||||||
2KD7 004 | 40 | 68 | 0.36 | ½" | 360 | 475 | 550 | 47 | ||
2KD7 006 | 60 | 100 | 0.36 | ½" | 360 | 475 | 550 | 47 | ||
2KD7 008 | 80 | 136 | 0.48 | 1" | 500 | 600 | 730 | 78 | ||
2KD7 010 | 100 | 170 | 0.60 | 1" | 500 | 600 | 730 | 90 | ||
2KD7 015 | 150 | 255 | 0.68 | 1" | 500 | 600 | 730 | 90 | ||
2KD7 020 | 200 | 340 | 1 | 1½" | 700 | 700 | 830 | 120 | ||
2KD7 025 | 250 | 425 | 1.4 | 1½" | 700 | 700 | 830 | 135 | ||
2KD7 030 | 300 | 510 | 1.4 | 1½" | 700 | 700 | 830 | 135 | ||
2KD7 040 | 400 | 680 | 1.8 | 2" NB flg | 900 | 900 | 1230 | 170 | ||
2KD7 050 | 500 | 850 | 2.2 | 2" NB flg | 900 | 900 | 1230 | 180 | ||
2KD7 075 | 750 | 1275 | 3.3 | 2" NB flg | 750 | 1000 | 1400 | 250 | ||
2KD7 100 | 1000 | 1700 | 4.2 | 2" NB flg | 900 | 1200 | 1475 |
* - Voltage 180 to 240 V in case of 1Ø; 380 to 450 V in case of 3Ø
# - Power Consumption considering 45° C inlet and 35° C ambient temp.
NOTE: For70 to 80 bar operating pressure, contact factory
Sizing Conversion Factors:
Inlet Temperature (C1)
Temperature °C | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
Correction Factor | 1.2 | 1.15 | 1.05 | 1.0 | 0.85 | 0.7 | 0.6 |
Ambient Temperature (C2)
Temperature | 25 | 30 | 35 | 40 | 45 | 50 |
Correction factor | 1.2 | 1.15 | 1.1 | 1.05 | 1.0 | 0.9 |
Inlet Pressure (C3)
Inlet Pressure | bar (g) | 4 | 5 | 6 | 7 | 8 | 9 | 10.5 | 11 | 12.5 | 13 | 14 | 15 | 16 |
psi (g) | 58 | 73 | 87 | 100 | 116 | 131 | 150 | 160 | 180 | 189 | 200 | 218 | 232 | |
Correction Factor | . | 0.75 | 0.85 | 0.95 | 1.00 | 1.06 | 1.04 | 1.07 | 1.18 | 1.09 | 1.22 | 1.12 | 1.25 | 1.14 |
Dew Point (C4)
Dewpoint in C | 3 | 7 | 10 |
Correction Factor | .0 | 1.15 | 1.3 |
Dryer Normal Capacity = | Actual Capacity × C4 |
C1 × C2 × C3 |
Operating conditions | Ideal | Maximum |
Inlet temperature | 45°C | 60°C |
Ambient Temperature | 35°C | 50°C |
Working pressure | 40 bar | 42 bar |
Pressure Dew point | 3°C | NIL |
* Product Design and specification subject to change due to constant upgradation.